Event 2 of 148: Event ID 16# 4301
Mode transition from STOP to STARTUP
STOP due to: STOP caused by PG stop operation or by SFB 20 "STOP"
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered via MPI; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic startup not permitted, corrections in parameter assignment, submodule, etc. necessary
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered via MPI; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
03:11:53.415 AM 07/15/2002
(Coding: 16# 4301 FF46 C772 4304 0814 1714)
Event 3 of 148: Event ID 16# 6547
Parameter assignment error assigning parameters to modules (not on P bus, cancel download)
no relevance for user: SDB number: 1003
DP master affected in rack 0 and slot 9
Station number: 0, slot number: 10
Operating mode: STOP (internal)
Internal error, Incoming event
03:11:53.376 AM 07/15/2002
(Coding: 16# 6547 FF04 C47B 03EB 0900 000A)
Event 4 of 148: Event ID 16# 6547
Parameter assignment error assigning parameters to modules (not on P bus, cancel download)
no relevance for user: SDB number: 1002
DP master affected in rack 0 and slot 9
Station number: 0, slot number: 10
Operating mode: STOP (internal)
Internal error, Incoming event
03:11:31.986 AM 07/15/2002
(Coding: 16# 6547 FF04 C47B 03EA 0900 000A)
Event 5 of 148: Event ID 16# 6547
Parameter assignment error assigning parameters to modules (not on P bus, cancel download)
no relevance for user: SDB number: 1001
DP master affected in rack 0 and slot 9
Station number: 0, slot number: 10
Operating mode: STOP (internal)
Internal error, Incoming event
03:11:10.616 AM 07/15/2002
(Coding: 16# 6547 FF04 C47B 03E9 0900 000A)
Event 6 of 148: Event ID 16# 6547
Parameter assignment error assigning parameters to modules (not on P bus, cancel download)
no relevance for user: SDB number: 1000
DP master affected in rack 0 and slot 9
Station number: 0, slot number: 10
Operating mode: STOP (internal)
Internal error, Incoming event
03:10:49.258 AM 07/15/2002
(Coding: 16# 6547 FF04 C47B 03E8 0900 000A)
手机扫码追踪该问题,
觉得实用,立即去分享!
点击复制链接
cp343不是紧挨cpu的?换到4试试
把以太网模块放在第4槽。资料参考,https://support.industry.siemens.com/cs/CN/zh/view/90276761
还不行就检查你的背板是不是有问题,u型连接器有可能有问题,有可能接触不好啥的